Title of your website

myDESIGNER USER MANUAL
  1. Introduction
    1. About myDESIGNER
  2. Tutorial videos
    1. myDESIGNER
    2. myREPORTS
    3. myMOBILE
  3. Getting started with myDESIGNER
    1. Creating a project
    2. Workspace management
  4. Checking project
  5. Projects’ visual appearance
  6. GUI/HMI Editor
    1. Creating views
    2. Selecting objects
    3. Drawing primitives
    4. Creating text elements
    5. Insert image
    6. Poly-lines
    7. Moving objects
    8. Resizing objects
    9. Rotating objects
    10. Skewing objects
    11. Filleting
    12. Combining objects
    13. Fill and stroke
    14. Rulers and guides
    15. Layers
    16. Copying and pasting elements
    17. Object's order
    18. Grouping
    19. Repeated actions mode
    20. View scripts
    21. Used tags
    22. Zoom on zone
    23. Undo and redo
    24. View properties
  7. Components
    1. Default components
    2. Custom components
    3. Used components
    4. Editing components
    5. Replacements
    6. On touch actions
    7. Entering advanced functions (equations)
  8. Components library
    1. Combo box, List box and Text box
      1. Inserting into view
      2. Components parameters
      3. Using components in view scripts
      4. Supported functions
    2. Chart component
  9. Active area
    1. Introduction
    2. Creating active areas
    3. External web page in active area
    4. HTML code
    5. DIV type
  10. Layout views
    1. Page layout
    2. Adding layout view
    3. Creating new layout
  11. Entering tags and math expressions
    1. Entering tags
    2. Entering mathematical expressions
  12. Tree tags database
    1. Changing tag value
    2. Engineering units
    3. Filtering data
    4. Usage count
    5. MS Excel import and export
    6. Tag import
    7. Deleting unused tags
    8. Restoring tag database
    9. Specifying a new tag during development
  13. Formatting numerical values
  14. Linking views with PLC
    1. Introduction
    2. Animations
    3. Show value animation
    4. Value to text mapping animation
    5. Visibility animation
    6. Opacity animation
    7. Color animation
    8. Moving animation
    9. Size animation
    10. Scale animation
    11. Rotate animation
    12. Circular sector animation
    13. Zoom visibility animation
    14. Sounds
    15. Sounds triggered by tag value
    16. Effects
  15. Time Sequence
    1. Example
    2. Triggering time sequences
    3. Modifying time settings
    4. Adding new sequences
    5. Renaming time sequence
    6. Switching among time sequence
    7. Modifying timing
    8. Combining multiple time sequences
  16. Open command
    1. Open type
    2. Target
    3. Popup (face plate) window
    4. View type
  17. Write/Set command
    1. Using batches
    2. Specifying set command parameters
    3. Value options
  18. Scaling set values
    1. Set example
  19. Key shortcuts
  20. On touch
    1. On touch in views
    2. On touch in component
    3. On touch example
    4. Lock element
    5. Lock key
    6. Slider
  21. Parametric views
    1. Opening parametric views
    2. Symbolic text replacements
    3. Symbolic tag creation
    4. Replacing connections
    5. Nesting parametric views
    6. Usage example:
  22. View scripts
    1. Using script in views
    2. Declaring variables
    3. Script writing
    4. Using variables in animations and effects
    5. Debugging view scripts
    6. Using debug screen on your view
    7. Using web browsers integrated debugger
    8. Using JavaScript libraries - Includes
    9. Linking external JavaScript libraries – Remote includes
  23. View scripts - list of functions
    1. Dealing with elements
    2. ListBox, TextBox and ComboBox functions
    3. Animations
    4. Effects
    5. Error frames
    6. Zoom
    7. Open command
    8. Users, language and login
    9. Retrieving files
    10. Communicating with server side scripts
    11. Tables
    12. Alarms and aggregated alarms
    13. Data - Log data
    14. Custom charts
    15. Tag info
    16. Other useful functions
  24. Documents
  25. Reports
    1. Creating report templates
    2. Designing report
    3. Inserting text
    4. Adding picture – logo
    5. Table data
    6. Table summary
    7. Previewing report during design
    8. Showing report in runtime
    9. Creating custom report in runtime
    10. Creating report on demand
  26. CAS alarms
    1. Digital alarms
    2. Analog alarms
    3. Alarm window
    4. Alarm history
      1. CAS alarms occurrence - Chart/Table
    5. CAS alarms in view - example
    6. CAS alarms preview of appearance
  27. Data logging
    1. Data - logs
    2. Defining connection
    3. Defining data points
    4. Continuous data logging
    5. Triggered data logs
    6. Triggered logging example
    7. Simple periodic export to CSV and Microsoft Power BI
    8. Data-logs properties
  28. Data - Log views
    1. Data points selection
    2. Data grouping
    3. Filtering data
    4. 3D chart
    5. Data-logs preview - appearance editor
  29. Aggregated data logs
    1. Creating aggregated data log
    2. Aggregated values:
    3. Time aggregates
    4. Value change aggregates
    5. Aggregates based on alarm activation
    6. Running the aggregation periodically
  30. Advanced trends
    1. Using multiple axes
    2. Advanced trends – visual appearance
    3. Gantt chart
  31. Connections
    1. Creating new connection
    2. Creating PLC type connection
    3. Creating database type connection
    4. Creating IoT type connection
    5. Deleting connections
    6. Advanced options - optimizations
  32. User accesses
    1. Access levels
    2. Access groups
    3. User accounts
    4. Limiting access for whole project
    5. Limited access for views and trends
    6. Limited access of arbitrary object in views
    7. User edit in runtime
    8. RFID
  33. Multi - language support
    1. Providing translations inside a project
    2. Translating names of Views
    3. Translating Data - logs
    4. Translating CAS alarms
    5. Translating advanced trends
  34. Server-side scripts
    1. Introduction
    2. Server-side scripts folder
    3. Server-side scripts folder structure
    4. Variables tables
    5. Script data-logs
    6. Global variables
    7. Sources folder
    8. Organizing project into modules
    9. Importing modules
    10. Using the event-driven asynchronous callbacks
    11. Creating server side reports
    12. mySCADA specific functions
    13. Debugging
    14. Script status (on myBOX devices only)
    15. Ser2Net (on myBOX devices only)
  35. View and server side scripts – common tasks
    1. Graphical guides
    2. Read/Write data from/to PLC
    3. Generating report
    4. Other guides
    5. Server side scripts – examples
    6. Reading data from PLC
    7. Writing data into PLC
    8. Timers – eg. run code in given time intervals
    9. Scheduled execution e.g run code every Monday at 2:00 PM
    10. Generating a report at given time interval
    11. Limiting access to generated files
    12. Processing data-log data
    13. Exporting data-log data into CSV files
    14. Using virtual PLC
    15. Sending data from view script into server side scripts
  36. Devices
  37. EtherNet/IP driver
  38. MicroLogix and SLC driver
  39. Modbus driver
    1. Tag name syntax
    2. 32-bit registers in Modbus
    3. Floating point numbers
    4. 32-bit integers
    5. Address mapping
    6. Signed and unsigned numbers
  40. Siemens S7 family PLCs driver
    1. Memory types
    2. S7 data types
    3. S7 1200/1500 notes
    4. Protection
    5. LOGO! 0BA7/0BA8 configuration
    6. S7-200 (via CP243-1) configuration
  41. OPC UA driver
    1. Connection configuration
    2. Tag name syntax
  42. MELSEC-Q driver
    1. Tag name syntax
    2. Connection settings
  43. SigFox driver
    1. Datatype
    2. Reverse order
  44. Databases driver
    1. Reading values from SQL database
    2. Examples
    3. Writing values to SQL database
    4. Using SQL connectivity in Server Side Scripts
  45. Download/Upload from/to device
    1. Download to device
    2. Upload from device
  46. Recipes
  47. Running hours
  48. Timeline
  49. mySCADA TIA portal connector

26.2.Analog alarms #

Analog alarms are tied to analog values read from the PLC. Along with common parameters, which are the same for both digital and analog alarms, you specify the minimum and maximum values for your tag or equation. You can also specify the Dead-band region for any value to eliminate false alarms. The number of alarms tied to one tag is not limited. In addition, you can define complex conditions, including multiple tags or mathematical conditions for a single alarm.

 

26.2.1

Description of Alarm table fields:

Unique ID

Automatically generated ID; needed if accessing alarms from the Server-side Script

Tag@Conn / *alias

Tag (Address) or Equation specifying data read from PLCs

Severity

Unsigned integer value specifying importance of given alarm; the lower the number, the higher the priority

Area

You can divide alarms by the geographical or virtual area they belong to; area is a string value that you can use to filter the alarms

Message

Message of your alarm

Device

Name or description of a device the alarm belongs to; one device can have multiple alarms defined

Inv (Inverse)

Inverts an alarm (if a digital alarm is inverted it will be active at 0; for analog alarm activation, area is reversed)

Hide

Enables hiding the alarm from the user; this is useful when you are using alarms as a condition in the triggered data-log; hidden alarms are not shown in the Alarm window and are not logged in the database.

Delay

Specifies the delay in milliseconds of how long the condition must be active to activate the alarm; this is the time hysteresis function

Refresh

Specifies how often your alarm will be refreshed; you can use default, fast, or slow. You can change the refresh values for each group in the Properties window.

 

Format

Defines how the value will be shown in the alarm table; use the ‘##.#’ format for specification

e-mail

Sends an email upon each alarm activation or deactivation

SMS Act

Sends a message upon each alarm activation

SMS Deact

Sends a message upon each alarm deactivation

G0 – G9

Checks appropriate user group to receive alarms by email or SMS

 

Unique ID

Each alarm has a Unique ID, which is created when you define a new alarm; its value is fixed once the project is put into the runtime mode for the first time. This value is unique for all alarms, meaning that each alarm has its own Unique ID that is saved in the alarms’ definition file. Once this ID has been created, it will remain until the alarm is removed from the definition table.

Tag@Conn / *alias

Each alarm must be connected to a tag or equation. The Tag is the value read from PLC (or your computed value from the script); with Equation, you can tie your alarm to multiple tags or evaluate complex formulas.

Specifying a tag:

26.2.2

 

Specifying a complex formula:

26.2.3

 

You can create multiple alarms tied to one tag, as long as the alarm descriptions are different so that alarms operate correctly.

Severity

Alarms can range in severity from 0 (most severe) up to an unsigned integer value (least severe), to indicate different levels of importance.

For example, an alarm with severity 10 might warn that a tank is half full of liquid, while another alarm with severity 5 indicates that the tank is about to overflow. Both alarms monitor the same tag but have different severity levels.

When you set up the alarm severity, specify what the severity levels mean and what actions they will trigger. Severity determines the order in which alarms are displayed in the alarm list.

Alarm areas

The alarms can be grouped in different areas so that they can be displayed in the alarm window based on the area to which they belong. This may be helpful and enable you to divide the alarms according to the different plant zones they come from.

Message

Alarm messages report information about alarms.

Device

You can define multiple alarms for a single device. In the live alarm view or during a browsing of alarm history, you can filter your data based on device value.

Minimum and Maximum values

Minimum and maximum values are available for analog alarms only. By default, you specify the region when the alarm will be active. So if you would like to activate an alarm when the level in a tank is equal to 90 and stop the alarm at level 100, your minimum value will be 90 and the maximum value will be 100.

Inv (Inverse)

This parameter lets you invert your alarm definition. For a digital alarm, the alarm is activated when the value is equal to 0 and deactivated when equal to 1. For analog alarms, when ‘inverse’ is active, you specify the minimum and maximum values of the region when the alarm is NOT active.

Recipients (G0 up to G9)

Through these properties, you can select the recipient user group to which the message, SMS, E-mail, etc. is to be sent. The user profile, which is defined through the ‘Users’ settings, must contain a telephone number or E-Mail for sending messages.

Dead-band

With some measured values, such as line pressure, tag values can fluctuate rapidly above and below a critical threshold. Where such conditions exist, you can create a dead band as a buffer to prevent the fluctuations from triggering unnecessary alarms.

 

26.2.4

 

Specifying frequency of alarm checks

The system does not check for alarms more frequently than the Refresh update rate specified in the alarm definition.

Match the maximum update rate to the rate at which you expect tag values to change. For example, if you are monitoring temperatures that fluctuate slowly, check alarms less frequently than when you have a manufacturing process that changes temperature rapidly.

You can specify one of three possible refresh rates: default, slow, or fast. Each refresh rate group can be changed in the Properties window.

26.2.5

 

Suggest Edit